V4-T3-64 Volume 4—Circuit Protection CA08100005E—April 2014 www.eaton.com
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3
3.2
Power Breakers, Contactors and Fuses
Medium Voltage Power Contactors
Product Specifications
7.2 kV/160–400A
Short-time current:
30 seconds: 2400A
1 second: 6000A
8.7 ms: 63 kA peak
(0.5 cycle)
Normal service altitude:
–3281 to +6562 ft (–1000
to +2000m)
Mechanical life: 2.5 million
Electrical life:
6 x Rated Make/1x Rated
Break: 300,000
operations
6 x Rated Make/6 x
Rated Break: 300,000
operations
BIL (impulse withstand):
60 kV (1.2 x 50
microseconds)
Dielectric strength: 20 kV
rms (1 minute)
Closing time: 80 ms
(energization to contact
touch)
Selectable opening times:
30 ms (2 cycles)
50 ms (3 cycles)
130 ms (8 cycles)
250 ms (15 cycles)
330 ms (20 cycles)
Arcing time: 12 ms
(0.75 cycle) or less
Pickup voltage: 80%
rated coil voltage
Dropout voltage: 60%
rated coil voltage
Control voltages:
AC/Hz: 110/50, 120/60,
220/50, 240/60
DC: 125
Control circuit burden:
Closing: (200 ms)
110/120 AC, 125 DC
1 kVA
220/240 AC 1.8 kVA
Holding:
110/120 AC, 125 DC
40 VA
220/240 AC 50 VA
Auxiliary contact rating:
600V (maximum)
10A continuous current
Making capacity
–AC: 7200 VA
DC: 125 VA
Breaking capacity
AC: 720 VA
DC: 125 VA
Latch (when specified)
Mechanical life: 250,000
operations
Trip vo l t a ge
–DC: 24V
DC: 125V
AC: 110/120V
Minimum trip voltage:
80% rated coil voltage
Trip burden
24 Vdc: 400 VA
48 and 125 Vdc:
400 VA
110 and 120 Vac:
400 VA
220 and 240 Vac:
400 VA
Trip time (2 cycles):
30 ms
Weight
150–360A: 47 lbs
(21.3 kg)
400A: 49 lbs (22.2 kg)
Wiring Diagrams
Electrical Connections Diagrams (7.2 kV/160–400A)
Connection for Magnetically Held Contactor Connections for Mechanically Latched Contactor
Note
1
M contacts are connected in parallel for
AC voltages and for
<
48 Vdc.
M contacts are connected in series for
>48 Vdc.
Control
Voltage
(On/Off)
White
Black
Black
White
DC
Coil 2
DC
Coil 1
11
2
3
4
5
6
7
8
Control
Voltage
(Close)
White
Black
Black
White
DC
Coil 2
DC
Coil 1
11
2
3
4
5
6
7
8
Control
Voltage
(Open)
(+)
(–)
DC Latch
Coil
M
M